Name
Range
Step
Default
Description
IDMT Const B
1(9) – 2(10)
0.01...25.00
0.01
1.00
Defines the IDMT constant B. Note that this setting is only visible
when the "Point 1(9)–2(10) characteristics" setting is set to "Two
point steps" or "Two point interpolate".
IDMT Const C
1(9) – 2(10)
0.01...25.00
0.01
1.00
Defines the IDMT constant C. Note that this setting is only visible
when the "Point 1(9)–2(10) characteristics" setting is set to "Two
point steps" or "Two point interpolate".
Operating
curve test
(online)
1.00...40.00
0.01
1.00
Allows the testing of the expected operating time with the given
I
meas
/I
set
value with an online relay.
The IDMT curve formula used to calculate the segment timing behaviour is shown below:
Below is an example of the programmable curve settings with three separate operating time segments.
1. RED: I
meas
/I
set
= 1.0…2.0, IDMT IEC-NI, time dial k = 0.05, IDMT constant A = 0.14, IDMT
constant B = 0.02, IDMT constant C = 0.0001.
2. BLUE: I
meas
/I
set
= 2.0…3.0, two point interpolate, time point = 3
3. YELLOW: I
meas
/I
set
= 3.0…5.0, definite time step, the set 3.0 s is held until the I
meas
/I
set
ratio
reaches 5.0, and after that the time point = 4 is used with the time setting 0.1 s.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
106
© Arcteq Relays Ltd
IM00040