Name
Range
Step
Default
Description
Continue
time
calculation
during
release
time
1: No
2: Yes
-
1: No
Time calculation characteristics selection. If activated, the operating time
counter is continuing until a set release time has passed even if the pick-
up element is reset.
The user can reset characteristics through the application. The default setting is a 60 ms delay; the
time calculation is held during the release time.
In the release delay option the operating time counter calculates the operating time during the release.
When using this option the function does not trip if the input signal is not re-activated while the release
time count is on-going.
Events and registers
The overvoltage function (abbreviated "OV" in event block names) generates events and registers from
the status changes in START, TRIP, and BLOCKED. The user can select which event messages are
stored in the main event buffer: ON, OFF, or both. The function offers four (4) independent stages;
the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.7 - 96. Event messages.
Event block name
Event names
OV1
Start ON
OV1
Start OFF
OV1
Trip ON
OV1
Trip OFF
OV1
Block ON
OV1
Block OFF
OV2
Start ON
OV2
Start OFF
OV2
Trip ON
OV2
Trip OFF
OV2
Block ON
OV2
Block OFF
OV3
Start ON
OV3
Start OFF
OV3
Trip ON
OV3
Trip OFF
OV3
Block ON
OV3
Block OFF
OV4
Start ON
OV4
Start OFF
OV4
Trip ON
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
140
© Arcteq Relays Ltd
IM00040