Event block name
Event names
VUB3
Start OFF
VUB3
Trip ON
VUB3
Trip OFF
VUB3
Block ON
VUB3
Block OFF
VUB4
Start ON
VUB4
Start OFF
VUB4
Trip ON
VUB4
Trip OFF
VUB4
Block ON
VUB4
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers; this information is
available for all provided instances separately. The register of the function records the ON event
process data for START, TRIP or BLOCKED. The table below presents the structure of the function's
register content.
Table. 5.4.10 - 120. Register content.
Date and time
Event
Pre-trigger
voltage
Fault
voltage
Pre-fault
voltage
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
Event
name
Start/Trip -20ms
voltage
Start/Trip
voltage
Start -200ms
voltage
0 ms...1800s
Setting group 1...8
active
5.4.11 Non-directional undercurrent protection (I<; 37)
The non-directional undercurrent function is used for instant and time-delayed undercurrent protection.
The operating decisions are based on phase current magnitude, constantly measured by the
function. The available phase current magnitudes are equal to RMS values. The blocking signal and the
setting group selection control the operating characteristics of the function during normal operation,
i.e. the user or user-defined logic can change function parameters while the function is running.
The function's outputs are START, TRIP and BLOCKED signals which can be used for direct I/O
controlling and user logic programming.. The undercurrent function uses a total of eight (8) separate
setting groups which can be selected from one common source.
The function can operate on instant or time-delayed mode. In the time-delayed mode the operation can
be set to operate on definite time (DT) delay.
The inputs for the function are the following:
• setting parameters
• digital inputs and logic signals
• measured and pre-processed current magnitudes.
The function outputs the START, TRIP and BLOCKED signals which can be used for direct I/O
controlling and user logic programming. The function generates general time-stamped ON/OFF events
to the common event buffer from each of the three (3) output signals. In the instant operating mode the
function outputs START and TRIP events simultaneously with an equivalent time stamp. The time stamp
resolution is 1 ms. The function also provides a resettable cumulative counter for the START, TRIP and
BLOCKED events.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00040