Name
Range
Step
Default
Description
Temp.
reference
(t
ref
)
k
amb
=1.0
-60…500deg
1deg
15deg
The temperature reference setting. The manufacturer's temperature
presumptions apply and the thermal correction factor is 1.00 (rated
temperature). For underground cables the set value for this is usually
15
̊
C and for cables in the air it is usually 25
̊
C.
This setting is visible if "Ambient lin. or curve" is set to "Linear est."
Max.
ambient
temp.
0…500deg
1deg
45deg
The maximum ambient temperature setting. If the measured
temperature is more than the maximum set temperature, the set
correction factor for the maximum temperature is used. This setting is
visible if "Ambient lin. or curve" is set to "Linear est."
k at max.
amb.
temp.
0.01…5.00xI
n
0.01xI
n
1.00xI
n
The temperature correction factor for the maximum ambient
temperature setting. This setting is visible if "Ambient lin. or curve" is set
to "Linear est."
Min.
ambient
temp.
-60…500deg
1deg
0deg
The minimum ambient temperature setting. If the measured temperature
is below the minimum set temperature, the set correction factor for
minimum temperature is used. This setting is visible if "Ambient lin. or
curve" is set to "Linear est."
k at min.
amb.
temp.
0.01…5.00xI
n
0.01xI
n
1.00xI
n
The temperature correction factor for the minimum ambient temperature
setting. This setting is visible if "Ambient lin. or curve" is set to "Linear
est."
Amb.
temp. ref.
1...10
-50.0…500.0deg 0.1deg 15deg
The temperature reference points for the user-settable ambient
temperature coefficient curve. This setting is visible if "Ambient lin. or
curve" is set to "Set curve".
Amb.
temp.
k1...k10
0.01…5.00
1.00
0.01
The coefficient value for the temperature reference point. The coefficient
and temperature reference points must be set as pairs. This setting is
visible if "Ambient lin. or curve" is set to "Set curve".
Add
curvepoint
3…10
0: Not used
1: Used
-
0: Not
used
The selection of whether or not the curve temperature/coefficient pair is
in use. The minimum number to be set for the temperature/coefficient
curve is two pairs and the maximum is ten pairs. If the measured
temperature is below the set minimum temperature reference or above
the maximum set temperature reference, the used temperature
coefficient is the first or last value in the set curve. This setting is visible
if "Ambient lin. or curve" is set to "Set curve".
Operation characteristics
The operating characteristics of the machine thermal overload protection function are completely
controlled by the thermal image. The thermal capacity value calculated from the thermal image can set
the I/O controls with ALARM 1, ALARM 2, INHIBIT and TRIP signals.
Table. 5.4.12 - 130. Pick-up settings.
Name
Range
Step
Default
Description
Enable
TF>
Alarm 1
0: Disabled
1: Enabled
-
0:
Disabled Enabling/disabling the ALARM 1 signal and the I/O.
TF>
Alarm 1
level
0.0…150.0%
0.1%
40%
ALARM 1 activation threshold.
Enable
TF>
Alarm 2
0: Disabled
1: Enabled
-
0:
Disabled Enabling/disabling the ALARM 2 signal and the I/O.
TF>
Alarm 2
level
0.0…150.0%
0.1%
40%
ALARM 2 activation threshold.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
182
© Arcteq Relays Ltd