General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.4.13 - 137. General settings of the function.
Name
Range
Default
Description
Channel
1
sensors
0: No
sensors
1: 1 sensor
2: 2 sensors
3: 3 sensors
1: No
sensors Defines the number of sensors connected to the channel (channels 1/2/3/4).
Channel
2
sensors
Channel
3
sensors
Channel
4
sensors
Channel
1 sensor
status
0: Sensors
OK
1:
Configuration
fault state
-
Displays the status of the sensor channel. If the number of sensors connected to the
channel does not match with the set "Channel 1/2/3/4 sensors" setting, this parameter
will go to the "Configuration fault" state.
Channel
2 sensor
status
Channel
3 sensor
status
Channel
4 sensor
status
Pick-up
The pick-up of each zone of the Iarc>/I0arc> function is controlled by one of the following: the phase
current pick-up setting, the residual current pick-up setting, or the sensor channels. The pick-up
setting depends on which of these are activated in the zone.
Table. 5.4.13 - 138. Enabled Zone pick-up settings.
Name
Description
Range
Step Default
Phase
current
pick-up
The phase current measurement's pick-up value (in p.u.).
0.05...40.00
x I
n
0.01
x I
n
1.2 x I
n
I0 input
selection
Selects the residual current channel (I01 or I02).
0: None
1: I01
2: I02
-
0: None
Res.current
pick-up
The residual current measurement's pick-up value (in p.u.).
0.05...40.00
x I
0n
0.01
x I
0n
1.2 x
I
0n
Zone1/2/3/
4 Enabled
Enables the chosen zone. Up to 4 zones can be enabled.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/
4 Ph. curr.
Enabled
The phase overcurrent allows the zone to trip when light is detected.
0: Disabled
1: Enabled
-
0:
Disabled