Events and registers
The current transformer supervision function (abbreviated "CTS" in event block names) generates
events and registers from the status changes in ALARM ACTIVATED and BLOCKED signals. The user
can select which event messages are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.6.1 - 176. Event messages.
Event block name
Event names
CTS1
Alarm ON
CTS1
Alarm OFF
CTS1
Block ON
CTS1
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers; this information is
available for all provided instances separately. The register of the function records the ON event
process data for ACTIVATED, BLOCKED, etc. The table below presents the structure of the function's
register content.
Table. 5.6.1 - 177. Register content.
Date
and time
Event
Trigger currents
Time to
CTSact
Fault type
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
Event
name
The phase currents (L1, L2 & L3), the residual
currents (I01 & I02), and the sequence currents
(I1 & I2) on trigger time.
Time remaining
before alarm
activation.
The status code
of the monitored
current.
Setting
group
1...8
active.
5.6.2 Voltage transformer supervision (60)
Voltage transformer supervision is used to detect errors in the secondary circuit of the voltage
transformer wiring and during fuse failure. This signal is mostly used as an alarming function or to
disable functions that require adequate voltage measurement.
The function uses a total of eight (8) separate setting groups which can be selected from one common
source. Also, the operating mode of the function can be changed via setting group selection.
The operational logic consists of the following:
• input magnitude processing
• threshold comparator
• block signal check
• time delay characteristics
• output processing.
The inputs of the function are the following:
• setting parameters
• measured and pre-processed voltage magnitudes.