• P< (under power)
• Prev> (reverse power)
• T> (thermal overload)
When any of these functions trip, the fault values and the fault type are displayed in the Mimic view. The
view can be enabled by activating the "VREC Trigger on"setting (
Tools
→
Events and logs
→
Set alarm
events). The resetting of the fault values is done by the input selected in the General menu.
Function keeps 12 latest recordings in memory. Recordings can be viewed in the HMI if "Fault registers"
view has been added with "Carousel designer" tool.
Figure. 5.6.6 - 168. 12 latest recordings can be accessed from HMI if "Fault registers" view has been enabled in "Carousel
designer" tool.
Measured input
The function block uses analog current and voltage measurement values. Based on these values, the
relay calculates the primary and secondary values of currents, voltages, powers, and impedances as
well as other values.
The user can set up to eight (8) magnitudes to be recorded when the function is triggered. An
overcurrent fault type, a voltage fault type, and a tripped stage can be recorded and reported straight
to SCADA.
NO
NOTE!
TE!
The available measurement values depend on the relay type. If only current analog
measurements are available, the recorder can solely use signals which only use current. The
same applies, if only voltage analog measurements are available.
Currents
Description
IL1 (ff), IL2 (ff), IL3 (ff), I01 (ff), I02
(ff)
The fundamental frequency current measurement values (RMS) of phase currents and
of residual currents.
IL1TRMS, IL2TRMS, IL3TRMS,
I01TRMS, I02TRMS
The TRMS current measurement values of phase currents and of residual currents.