• Report Control Blocks (both buffered and unbuffered reporting)
• Control ('Direct operate with normal security’, ’Select before operate with normal
security, ’Direct with enhanced security’ and ’Select before operate with enhanced
sequrity’ control sequences)
• Disturbance recording file transfer
• GOOSE
• Time synchronization
The device's current IEC 61850 setup can be viewed and edited with the IEC61850 tool (
Tools
→
Communication
→
IEC 61850).
Settings.
The general setting parameters for the IEC 61850 protocol are visible both in AQtivate and in the local
HMI. The settings are described in the table below.
Table. 6.1.5 - 224. General settings.
Name
Range
Step Default
Description
Enable IEC 61850
0: Disabled
1: Enabled
-
0:
Disabled Enables and disables the IEC 61850 communication protocol.
Reconfigure IEC 61850
0: -
1: Reconfigure
-
0: -
Reconfigures IEC 61850 settings.
IP port
0…65 535
1
102
Defines the IP port used by the IEC 61850 protocol.
The standard (and default) port is 102.
IEC61850 edition
0: Ed1
0: Ed2
-
-
Displays the IEC61850 edition used by the device. Edition can
be chosen by loading a new CID file at
Tools
→
Communication
→
IEC 61850 with Open button.
Control Authority switch
0: Remote
Control
1: Station
Level Control
-
0:
Remote
Control
The device can be set to allow object control via IEC 61850
only from clients that are of category Station level control. This
would mean that other Remote control clients would not be
allowed to control. In Remote control mode all IEC 61850
clients of both remote and station level category are allowed
to control objects.
Ethernet port
0: All
1: COM A
2: Double
ethernet card
-
0: All
Determines which ports use IEC61850.
Configure GOOSE
Subscriber from CID file
allowed
0: Disabled
1: Allowed
-
0:
Disabled
In edition 2 of IEC 61850 GOOSE subscriber configuration is
a part of the CID file. Determines if it is possible to import
published GOOSE settings of another device with a CID file
and set them to GOOSE input at
Tools
→
Communication
→
IEC 61850
→
GOOSE subscriptions.
General deadband
0.1…10.0 %
0.1
%
2 %
Determines the general data reporting deadband settings.
Active energy deadband 0.1…1000.0
kWh
0.1
kWh
2 kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0
kW
0.1
kW
2 kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0
kVA
0.1
kVA
2 kVA
Determines the data reporting deadband settings for this
measurement.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00040
275