Table. 6.1.6 - 226. General GOOSE subscriber settings.
Name
Range
Description
GOOSE subscriber enable
0: Disabled
(Default)
1: Enabled
Enables or disables GOOSE subscribing for the device.
Not used GOOSE input
Quality
1: Bad
quality (1)
2: Good
quality (0)
Defines what state should GOOSE input quality signal to be in the logic if the
input has been set as "disabled".
Subscriber checks
GoCBRef
0: No
(Default)
1: Yes
When subscriber sees GOOSE frame it checks APPID and Conf. Rev but can
also check if GoCBRef or SqNum match.
Subscriber checks SqNum
Subscriber process
simulation messages
0: No
(Default)
1: Yes
Subscriber can be set to process frames which are published with simulation bit
high if enabled
GOOSE input settings
The table below presents the different settings available for all 64 GOOSE inputs.
Table. 6.1.6 - 227. GOOSE input settings.
Name
Range
Description
In use
0: No
(Default)
1: Yes
Enables and disables the GOOSE input in question.
Application
ID
("AppID")
0×0…0×3FFF Defines the application ID that will be matched with the publisher's GOOSE control block.
Configuration
revision
("ConfRev")
1…2
32
-1
Defines the configuration revision that will be matched with the publisher's GOOSE control
block.
Data index
("DataIdx")
0…99
Defines the data index of the value in the matched published frame. It is the status of the
GOOSE input.
NextIdx is
quality
0: No
(Default)
1: Yes
Selects whether or not the next received input is the quality bit of the GOOSE input.
Data type
0: Boolean
(Default)
1: Integer
2: Unsigned
3: Floating
point
Selects the data type of the GOOSE input.
Control block
reference
-
GOOSE subscriber can be set to check the GCB reference of the published GOOSE frame.
This setting is automatically filled when Ed2 GOOSE configuration is done by importing cid file
of the publisher.
GOOSE input descriptions
GOOSE inputs can be given a description. The user defined description are displayed in most of the
menus (logic editor, matrix, block settings etc.).
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00040
277