Table. 6.1.6 - 228. GOOSE input user description.
Name
Range
Default
Description
User editable
description GI x
1...31
characters
GOOSE
IN x
Description of the GOOSE input. This description is used in several menu
types for easier identification.
GOOSE events
GOOSE signals generate events status changes. The user can select which event messages are
stored in the main event buffer: ON, OFF, or both. The events triggered by the function are recorded
with a time stamp and with process data values. The time stamp resolution is 1 ms.
Table. 6.1.6 - 229. GOOSE event
Event block name
Event name
GOOSE1...GOOSE2
GOOSE IN 1...64 ON/OFF
GOOSE3...GOOSE4
GOOSE IN 1...64 quality Bad/Good
Setting the publisher
The configuration of the GOOSE publisher is done using the IEC 61850 tool in AQtivate (
Tools
→
Communication
→
IEC 61850). Refer to AQtivate-200 Instruction manual for more information on how
to set up GOOSE publisher.
6.1.7 IEC 103
IEC 103 is the shortened form of the international standard IEC 60870-5-103. The AQ-200 series units
are able to run as a secondary (slave) station. The IEC 103 protocol can be selected for the serial ports
that are available in the device. A primary (master) station can then communicate with the Arcteq
device and receive information by polling from the slave device. The transfer of disturbance recordings
is not supported.
NO
NOTE
TE: Once the configuration file has been loaded, the IEC 103 map of the relay can be found in the
AQtivate software (
Tools
→
IEC 103 map).
The following table presents the setting parameters for the IEC 103 protocol.
Name
Range
Step
Default
Description
Slave address
1…254
1
1
Defines the IEC 103 slave address for the unit.
Measurement interval
0…60 000ms
1ms
2000ms
Defines the interval for the measurements update.
6.1.8 DNP3
DNP3 is a protocol standard which is controlled by the DNP Users Group (www.dnp.org). The
implementation of a DNP3 slave is compliant with the DNP3 subset (level) 2, but it also contains some
functionalities of the higher levels. For detailed information please refer to the DNP3 Device Profile
document (
→
AQ-200 series
→
Resources).
Settings
The following table describes the DNP3 setting parameters.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
278
© Arcteq Relays Ltd
IM00040