Reset
Reset ratio
97 or 103 % of the pick-up voltage setting
Reset time setting
Inaccuracy: Reset time
0.010…10.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
9.2.1.11 Line thermal overload protection (TF>; 49F)
Table. 9.2.1.11 - 280. Technical data for the line thermal overload protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
TRMS phase currents (up to the 31
st
harmonic)
Settings
Time constants τ
1
Time constant value
0.0…500.00 min, step 0.1 min
Service factor (maximum overloading)
0.01…5.00 × I
N
, step 0.01 × I
N
Thermal model biasing
- Ambient temperature (Set –60.0…500.0 deg, step 0.1 deg and RTD)
- Negative sequence current
Thermal replica temperature estimates
Selectable between °C and °F
Outputs
- Alarm 1
- Alarm 2
- Thermal trip
- Trip delay
- Restart inhibit
0…150 %, step 1 %
0…150 %, step 1 %
0…150 %, step 1 %
0.000…3600.000 s, step 0.005 s
0…150 %, step 1 %
Inaccuracy
- Starting
- Operating time
±0.5 % of the set pick-up value
±5 % or ± 500 ms
9.2.1.12 Non-directional undercurrent protection (I<; 37)
Table. 9.2.1.12 - 281. Technical data for the undercurrent function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
RMS phase currents
Pick-up
Pick-up current setting
0.10…40.00 × I
N
, setting step 0.10 × I
N
Inaccuracy:
- Current
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operation time
Definite time function operating time setting
0.00…150.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 0.95)
±1.0 % or ±30 ms
Instant operation time
A
AQ
Q-C215
-C215