Table. 5.3.13 - 127. Setting parameters for reset time characteristics.
Name
Range
Step
Default
Description
Release
time delay
0.000…150.000s 0.005s 0.06s
Resetting time. Time allowed between pick-ups if the pick-up has not led
to a trip operation. During this time the START signal is held on for the
timers if the delayed pick-up release is active.
Delayed
pick-up
release
1: No
2: Yes
-
2: Yes
Resetting characteristics selection either as time-delayed or as instant
after the pick-up element is released. If activated, the START signal is
reset after a set release time delay.
Time calc
reset after
release
time
1: No
2: Yes
-
2: Yes
Operating timer resetting characteristics selection. When active, the
operating time counter is reset after a set release time if the pick-up
element is not activated during this time. When disabled, the operating
time counter is reset directly after the pick-up element reset.
Continue
time
calculation
during
release
time
1: No
2: Yes
-
1: No
Time calculation characteristics selection. If activated, the operating time
counter continues until a set release time has passed even if the pick-up
element is reset.
The user can reset characteristics through the application. The default setting is a 60 ms delay; the
time calculation is held during the release time.
In the release delay option the operating time counter calculates the operating time during the release.
When using this option the function does not trip if the input signal is not re-activated while the release
time count is on-going.
Events and registers
The sequence voltage function (abbreviated "VUB" in event block names) generates events and
registers from the status changes in START, TRIP and BLOCKED. The user can select which event
messages are stored in the main event buffer: ON, OFF, or both. The function offers four (4)
independent stages; the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.13 - 128. Event codes.
Event number
Event channel
Event block name
Event code
Description
8320
130
VUB1
0
Start ON
8321
130
VUB1
1
Start OFF
8322
130
VUB1
2
Trip ON
8323
130
VUB1
3
Trip OFF
8324
130
VUB1
4
Block ON
8325
130
VUB1
5
Block OFF
8384
131
VUB2
0
Start ON
8385
131
VUB2
1
Start OFF
8386
131
VUB2
2
Trip ON
8387
131
VUB2
3
Trip OFF
8388
131
VUB2
4
Block ON
8389
131
VUB2
5
Block OFF
8448
132
VUB3
0
Start ON
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
194
© Arcteq Relays Ltd
IM00013
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......