Setting example
Let us examine the settings, using a low-duty vacuum circuit breaker (ISM25_LD_1/3) manufactured
by Tavrida as an example. The image below presents the technical specifications provided by the
manufacturer, with the data relevant to our settings highlighted in red:
Now, we set the stage as follows:
Parameter
Setting
Current 1
0.80 kA
Operation 1
30 000 operations
Current 2
16.00 kA
Operations 2
100 operations
Enable Alarm 1
1: Enabled
Alarm 1 Set
1000 operations
Enable Alarm 2
1: Enabled
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
332
© Arcteq Relays Ltd
IM00013
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......