• Time synchronization
The device's current IEC 61850 setup can be viewed and edited with the IEC61850 tool (
Tools
→
Communication
→
IEC 61850). By browsing the 61850 tree one can see the full list of available logical
nodes in the Arcteq implementation.
Settings.
The general setting parameters for the IEC 61850 protocol are visible both in AQtivate and in the local
HMI. The settings are described in the table below.
Table. 6.1.4 - 289. General settings.
Name
Range
Step
Default
Description
Enable IEC 61850
0: Disabled
1: Enabled
-
0:
Disabled
Enables and disables the IEC 61850 communication
protocol.
IP port
0…65 535
1
102
Defines the IP port used by the IEC 61850 protocol.
The standard (and default) port is 102.
General deadband
0.1…10.0%
0.1%
2%
Determines the general data reporting deadband settings.
Active energy deadband 0.1…1000.0kWh 0.1kWh 2kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0kW
0.1kW
2kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0kVA
0.1kVA
2kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00Hz
0.01Hz
0.1Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00A
0.01A
5A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00A
0.01A
0.2A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband 0.1…5.0deg
0.1deg
1deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000ms
1ms
0ms
Defines the integration time of the protocol. If this
parameter is set to "0 ms", no integration time is in use.
Reconfigure GOOSE
0: -
1: Reconfigure
-
0: -
Reconfigures the GOOSE.
Enable GOOSE
subscriber
0: Disabled
1: Enabled
-
0:
Disabled Enabled and disables the GOOSE subscriber.
For more information on the IEC 61850 communication protocol support, please refer to the
conformance statement documents (
→
AQ-200 series
→
Resources).
A
AQ
Q-F215
-F215
Instruction manual
Version: 2.04
412