Operating time characteristics
The operating timers’ behavior of the function is set depending of the application. Both timers are
started from the same pick-up signal, which means that in case Retrip is used the time grading should
be set so that the Retrip time added with expected operating time and releasing time of the CBFP pick
up conditions is shorter than the set CBFP time in order to avoid unnecessary CBFP in cases when re
tripping to another breaker coil clears the fault. In the following table are presented the setting
parameters for the function time characteristics.
Table. 5.4.9. - 102. Operating time characteristics setting parameters.
Name
Range
Step
Default
Description
Retrip
0:No
1:Yes
-
Yes
Retrip enabled or disabled. If Retrip is disabled the output will not be visible and
also the TRetr setting parameter will not be available.
Retrip
time
delay
0.000…
1800.000s
0.005s 0.100s
Retrip start timer, this setting de nes how long the starting condition has to last
before RETRIP signal is activated.
CBFP
0.000…
1800.000s
0.005s 0.200s
CBFP start timer, this setting de nes how long the starting condition has to last
before CBFP signal is activated.
A few typical cased of CBFP are presented in the following gures.