Figure. 5.4.9. - 57. CBFP when selected criteria is current only.
In case when the current based protection activates so that either Iset and/or I0Sset current threshold
setting is exceeded, the counter for CBFP start to calculate the set operating time. The tripping of the
primary protection stage is not monitored in this con guration and if the current is not decreased under
the setting limit CBFP will be issued to upstream breaker. If the primary protection function clears the
fault e.g. the circuit breaker operates normally the counter for CBFP are reset immediately the current
is measured below the threshold settings.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
110