5505
86
OV2
1
Start OFF
5506
86
OV2
2
Trip ON
5507
86
OV2
3
Trip OFF
5508
86
OV2
4
Block ON
5509
86
OV2
5
Block OFF
5568
87
OV3
0
Start ON
5569
87
OV3
1
Start OFF
5570
87
OV3
2
Trip ON
5571
87
OV3
3
Trip OFF
5572
87
OV3
4
Block ON
5573
87
OV3
5
Block OFF
5632
88
OV4
0
Start ON
5633
88
OV4
1
Start OFF
5634
88
OV4
2
Trip ON
5635
88
OV4
3
Trip OFF
5636
88
OV4
4
Block ON
5637
88
OV4
5
Block OFF
In the register of the OV function is recorded start, trip or blocked “On” event process data. In the table
below is presented the structure of OV function register content. This information is available in 12 last
recorded events for all provided instances separately.
Table. 5.4.11. - 116. Register content.
Date & Time
Event
code
Fault
type
Trigger
voltage
Fault
voltage
Prefault
voltage
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
5440-5637
Descr.
L1-… L1-
L2-L3
Start average
voltage
Trip -20 ms
averages
Start -200ms
averages
0s ...1800s
1 - 8
5.4.12. Undervoltage U< (27)
Undervoltage function (UV) is used for instant- and time delayed undervoltage protection for various
applications including feeder, lter and machine applications of utilities and industry. Each IED with
voltage protection module has four available instances of the function (U<, U<<, U<<<, U<<<<).
Function constantly measures phase voltage- or line to line voltage magnitudes. Undervoltage
protection is based to line- to line fundamental frequency component or line- to neutral fundamental
frequency component if so chosen. If protection is based to line- to line voltage, during earth fault in
isolated or compensated networks the undervoltage protection is not affected. Undervoltage protection
stage has two blocking instances, internal blocking based on voltage measurement and low voltage or
external blocking during for example VT fuse failure. Blocking signal and setting group selection
controls the operating characteristics of the function during normal operation.
Outputs of the function are Start Trip and Blocked signals. Setting parameters are static inputs for the
function which are changed only by user input in the setup phase of the function. Undervoltage
function utilizes total of eight separate setting groups which can be selected from one common source.
The function can operate on instant or time delayed mode. In time delayed mode the operation can be
selected for de nite time or IDMT.
The operational logic consists of input magnitude processing, input magnitude selection, threshold
comparator, two block signal check, time delay characteristics and output processing.
AQ-F255
Instruction manual
Version: 2.00
127