Time calc
reset after
release time
No
Yes
-
Yes
Operating timer resetting characteristics selection. When active the
operating time counter is reset after set release time if pick-up element is
not activated during this time. When disabled the operating time counter is
reset directly after the pick-up element reset.
Continue time
calculation
during release
time
No
Yes
-
No
Time calculation characteristics selection. If activated the operating time
counter is continuing until set release time even the pick-up element is reset.
Resetting characteristics can be set according to the application. Default setting is delayed with 60 ms
and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the operating time
during the release time, function will not trip if the input signal is not activated again during the release
time counting.
Events and registers
The UV function generates events and registers from the status changes of start, trip and blocked. To
main event buffer is possible to select status “On” or “Off” messages. The UV function offers four
independent instances which events are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function (start, trip or
blocked) is recorded with time stamp and process data values.
Table. 5.4.12. - 122. Event codes of UV function instance 1 – 4.
Event Number
Event channel
Event block name
Event Code
Description
5696
89
UV1
0
Start ON
5697
89
UV1
1
Start OFF
5698
89
UV1
2
Trip ON
5699
89
UV1
3
Trip OFF
5700
89
UV1
4
Block ON
5701
89
UV1
5
Block OFF
5702
89
UV1
6
Undervoltage Block On
5703
89
UV1
7
Undervoltage Block Off
5760
90
UV2
0
Start ON
5761
90
UV2
1
Start OFF
5762
90
UV2
2
Trip ON
5763
90
UV2
3
Trip OFF
5764
90
UV2
4
Block ON
5765
90
UV2
5
Block OFF
5766
90
UV2
6
Undervoltage Block On
5767
90
UV2
7
Undervoltage Block Off
5824
91
UV3
0
Start ON
5825
91
UV3
1
Start OFF
5826
91
UV3
2
Trip ON
5827
91
UV3
3
Trip OFF
5828
91
UV3
4
Block ON
5829
91
UV3
5
Block OFF
AQ-F255
Instruction manual
Version: 2.00
133