Table. 5.4.17. - 147. Event codes of the OPW function.
Event Number
Event channel
Event block name
Event Code
Description
6400
100
OPW1
0
Start ON
6401
100
OPW1
1
Start OFF
6402
100
OPW1
2
Trip ON
6403
100
OPW1
3
Trip OFF
6404
100
OPW1
4
Block ON
6405
100
OPW1
5
Block OFF
In the register of the OPW function is recorded start, trip or blocked “On” event process data. In the
table below is presented the structure of OPW function register content. This information is available in
12 last recorded events for all provided instances separately.
Table. 5.4.17. - 148. Register content.
Date & Time
Event code
Trigger
power
Fault power
Prefault power
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
6400-
6405 Descr.
Start average
power
Trip -20ms
averages
Start -200 ms
averages
0ms -1800s
1 - 8
5.4.18. Under power P< (32U)
Under power function (UPW) is used for instant- and time delayed active under power protection.
Under power function detects loss-of-load conditions when there is no signi cant loss of current.
Outputs of the function are Start Trip and Blocked signals. Setting parameters are static inputs for the
function which are changed only by user input in the setup phase of the function. Under power function
utilizes total of eight separate setting groups which can be selected from one common source.
The operational logic consists of input magnitude processing, threshold comparator, two block signal
check, time delay characteristics and output processing.
Inputs for the function are the operating mode selections, setting parameters and measured and pre-
processed power magnitudes and binary input signals. Function outputs START, TRIP and BLOCKED
signals which can be used for direct IO controlling and also for user logic programming. The function
registers its operation into 12 last time-stamped registers and also generates general time stamped
ON/OFF events to the common event buffer from each of the three output signal. In instant operating
mode the function outputs START and TRIP events simultaneously with equivalent time stamp. Time
stamp resolution is 1ms. Function provides also cumulative counters for START, TRIP and BLOCKED
events.
In the following gure is presented the simpli ed function block diagram of the UPW function.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
156