Figure. 5.4.23. - 110. An IED equipped with arc protection card has 4 sensor channels. Up to three sensors can be connected to
each channel.
Arc protection card has four sensor channels. Up to three arc point sensors may be connected to each
channel. Sensor channels support Arcteq AQ-01 (light sensing) and AQ-02 (pressure and light
sensing) units. Optionally protection function can be applied with phase or residual current condition.
This means the function will trip only if light and over current conditions are met.
Outputs of the function are Light In, Pressure In, Arc binary input signal status, Zone trip, Zone blocked
and sensor fault signals. Setting parameters are static inputs for the function which are changed only
by user input in the setup phase of the function. Arc protection utilizes total of eight separate setting
groups which can be selected from one common source.
Table. 5.4.23. - 174. Output signals of the arc protection function
Outputs
Activation condition
Channel1 Light In
Channel2 Light In
Channel3 Light In
Channel4 Light In
Arc protection card sensor channel detects light.
Channel1 Pressure In
Channel2 Pressure In
Channel3 Pressure In
Channel4 Pressure In
Arc protection card sensor channel detects light.
ARC Binary input signal
Arc protection card binary input is energized.
I/I0 Arc> Ph.Curr.START
I/I0 Arc>
Res.Curr.START
Measured phase or residual current is over the set limit.
I/I0 Arc>
Ph.Curr.BLOCKED
I/I0 Arc>
Res.Curr.BLOCKED
Phase or residual current measurement is blocked by an input.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd