Withdrawable CB
Position indication
WD cart position
Control
Object ready
Use synchrocheck
Interlocks
Withdrawable circuit breaker monitor and control con guration.
Circuit Breaker
Position indication
Control
Object ready
Use synchrocheck
Interlocks
Circuit breaker monitor and control con guration.
Disconnector (MC)
Position indication
Control
Disconnector position monitoring and control of the disconnector
Disconnector (NC)
Position indication
Earthing switch position indication
In the following table are presented the setting parameters for withdrawable breaker con guration
(maximum set of parameters).
Table. 5.5.2. - 188. Object setting parameters
Name
Range
Step Default
Description
Object type
Withdrawable
CB
Circuit
Breaker
Disconnector
(MC)
Disconnector
(NC)
-
-
User selection of object type. Selection de nes the amount of required
binary inputs for the monitored object. This affects into the HMI and also
for the monitoring of the CB, WD cart in or out and if object ready is in use
or just monitoring of status (E.switch).
Use
Synchrocheck
No
Yes
-
No
Selection if synchrocheck condition is in use for circuit breaker close
command.
Sync timeout
0.000…
1800.000s
0.02s 0.2s
Setting for synchrocheck wait timeout. If the synchrocheck permission is
not received during this set time the close command will be rejected with
error message. (visible only if Use Synchrocheck is “Yes”)
Use Object
ready
Ready High
Ready Low
Not in use
-
Not in
use
Selection if object ready condition is in use for circuit breaker close
command. Selection can be either “1” or “0” for object ready or not in
use.
Breaker
traverse time
0.02…
500.00s
0.02s 0.2s
Maximum time between open and close status when breaker switches. If
this time is exceeded and both open and closed status inputs are active
status Bad is activated. If neither of the status inputs are active after the
delay Intermediate status is activated.
Sync wait
timeout
0.02…
500.00s
0.02s 0.2s
If synchronization ok is not received during this set time the close
command will be rejected with error message. (visible only if Use
synchrocheck is set to “In use”)
Obj Ready
wait timeout
0.000…
500.00s
0.02s 0.2s
If the object ready is not received during this set time the close command
will be rejected with error message. (visible only if Use Object is either
“High” or “Low”)
Max Close
pulse length
0.000…
500.00s
0.02s 0.2s
Maximum length for close pulse from the output relay to the controlled
object. If the object operates faster than this set time the control pulse will
be reset status change is detected.
Max Open
pulse length
0.000…
500.00s
0.02s 0.2s
Maximum length for open pulse from the output relay to the controlled
object. If the object operates faster than this set time the control pulse will
be reset status change is detected.
Control
termination
timeout
0.000…
500.00s
0.02s 10s
Control pulse termination timeout. If the object has not changed it status
in this given time the function will issue error event and the control is
ended. This parameter is common for both open and close commands.
Final Trip
pulse length
0.000…
500.00s
0.02s 0.2s
When nal trip is executed by the object ObjectX Final Trip signal
activates. If this parameter is set to 0s the signal is continuous. This can
be used in the matrix or the logic editor.
The pick-up activation of the function is not directly equal to start-signal generation of the function.
Start signal is allowed if blocking condition is not active.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
214