Blocking and interlocking
For each controllable object can be set interlocking and blocking conditions for open and close
separately. Blocking and interlocking can be based on other object statuses, software function or
binary input. For example, interlocking can be set for object close based on earthing disconnector
position.
Figure. 5.5.2. - 122. Example of interlock application. Closed earthing switch interlocks CB close.
Blocking signal has to reach the function 5 ms before control command in order it is received in time.
Events and registers
The OBJ function generates events and registers from the status changes of monitored signals as well
as control command fails and operations. To main event buffer it is possible to select status “On” or
“Off” messages.
In the function is available 12 last registers where the triggering event of the function is recorded with
time stamp and process data values.
Table. 5.5.2. - 189. Event codes of the OBJ function instances 1 – 10.
Event block name
Description
OBJ 1...10
Object Intermediate
OBJ 1...10
Object Open
OBJ 1...10
Object Close
OBJ 1...10
Object Bad
OBJ 1...10
WD Intermediate