I02 CT
secondary
0.001…
10.0A
0.00001A 5.0A
Rated secondary current of the CT in amperes.
I02 Polarity 0:-
1:Invert
-
0:-
I02 ( ne residual) measurement channel polarity (direction) selection.
Default setting is that positive current flow is from connector 9 to connector
10.
CT scaling
factor P/S
-
-
-
IED feedback value, this is the calculated scaling factor for primary
/secondary current ratio
Measurements
Following measurements are available from the measured current channels.
Table. 5.2.1. - 10. Per unit phase current measurements.
Name
Range
Step
Description
Phase current ILx
0.00…
1250.0xIn
0.01xIn Per unit measurement from each phase current channel fundamental
frequency RMS current.
Phase current ILx
TRMS
0.00…
1250.0xIn
0.01xIn
Per unit measurement from each current channel TRMS current including
harmonics up to 31
st
.
Peak to peak
current ILx
0.00…
500.0xIn
0.01xIn Per unit measurement peak to peak current from each phase current
measurement channel.
Table. 5.2.1. - 11. Primary phase current measurements.
Name
Range
Step
Description
Primary Phase
current ILx
0.00…
1000000.0A
0.01A Primary measurement from each phase current channel fundamental
frequency RMS current.
Phase current ILx
TRMS pri
0.00…
1000000.0A
0.01A
Primary measurement from each current channel TRMS current including
harmonics up to 31
st
.
Table. 5.2.1. - 12. Secondary phase current measurements.
Name
Range
Step
Description
Secondary Phase
current ILx
0.00…
300.0A
0.01A Secondary measurement from each phase current channel fundamental
frequency RMS current.
Phase current ILx
TRMS sec
0.00…
300.0A
0.01A
Secondary measurement from each current channel TRMS current including
harmonics up to 31
st
.
Table. 5.2.1. - 13. Phase current angles measurements.
Name
Range
Step
Description
Phase angle ILx
0.00…360.00deg
0.01deg
Phase angle measurement of the three phase current inputs.
Table. 5.2.1. - 14. Per unit residual current measurements.
Name
Range
Step
Description
Residual current
I01
0.00…
1250.0xIn
0.01xIn Per unit measurement from residual current channel I01 fundamental
frequency RMS current.
Residual current
I02
0.00…
1250.0xIn
0.01xIn Per unit measurement from residual current channel I02 fundamental
frequency RMS current.
Calculated I0
0.00…
1250.0xIn
0.01xIn Per unit measurement from calculated I0 current fundamental frequency RMS
current.
Phase current I01
TRMS
0.00…
1250.0xIn
0.01xIn
Per unit measurement from I01 residual current channel TRMS current
including harmonics up to 31
st
.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
22