Figure. 5.5.5. - 142. Example of timers and pick-up parameters. Normal CLPU situation.
CLPU activates after current has been under ILow setting for time Tset . When current exceed the
IHigh setting the maximum allowed CLPU timer start to count until Tmax time. In this example the pick-
up current is cleared before the Tmax time. When the measured current is in between of ILow and
IHigh the start-up condition is considered to be over. The CLPU signal can be prolonged over this time
by setting Tmin to higher value than 0.000s.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
244