Figure. 5.5.5. - 144. Example of timers and pick-up parameters. Activated CLPU instant release due to overcurrent.
CLPU activates after current has been under ILow setting for time Tset . When current exceed the
IHigh setting the maximum allowed CLPU timer start to count until Tmax time. In this example the
measured current is exceeding the IOver setting during the startup situation and causes the CLPU
signal immediate release.