Figure. 5.5.5. - 147. Example of timers and pick-up parameters. Inrush current is detected during Tmin time.
CLPU activates after current has been under ILow setting for time Tset. When current exceed the ILow
setting but not IHigh the CLPU signal is active until the Tmin time. When the current exceed the IHigh
setting the Tmax timer is started. CLPU signal will stay active until the Tmax time is used or the start-up
is over and Tmin time is over.
Events and registers
The CLPU function generates events and registers from the status changes of CLPU activated and
blocked signals as well as from the internal pick-up comparators. To main event buffer is possible to
select status “On” or “Off” messages.
Function includes 12 last registers where the triggering event of the function (CLPU activated or
blocked) is recorded with time stamp and process data values.
Table. 5.5.5. - 201. Event codes of the CLPU function
Event Number
Event channel
Event block name
Event Code
Description
2688
42
CLP1
0
LowStart ON
2689
42
CLP1
1
LowStart OFF
2690
42
CLP1
2
HighStart ON
2691
42
CLP1
3
HighStart OFF
2692
42
CLP1
4
LoadNormal ON
AQ-F255
Instruction manual
Version: 2.00
249
© Arcteq Relays Ltd