Where “Ix” is phase or residual current magnitude and “φ” is the angle difference between the phase or
residual voltage and current.
Following measurements are available from the measured current channels.
Table. 5.2.1. - 23. Per unit phase current component measurements.
Name
Range
Step
Description
ILx Resistive Current
p.u.
-1250.00…
1250.0xIn
0.01xIn Per unit measurement from each phase current channel resistive
current component.
ILx Reactive Current p.u. -1250.00…
1250.0xIn
0.01xIn Per unit measurement from each phase current channel reactive
current component.
Pos.Seq Resistive
Current p.u.
-1250.00…
1250.0xIn
0.01xIn Per unit measurement from each phase current channel resistive
current component.
Pos.Seq Reactive
Current p.u.
-1250.00…
1250.0xIn
0.01xIn Per unit measurement from each phase current channel reactive
current component.
I01 Resistive Current
p.u.
-1250.00…
1250.0xIn
0.01xIn Per unit measurement from residual current channel I01 resistive
current component.
I01 Reactive Current
p.u.
-1250.00…
1250.0xIn
0.01xIn Per unit measurement from residual current channel I01 reactive
current component.
I02 Resistive Current
p.u.
-1250.00…
1250.0xIn
0.01xIn Per unit measurement from residual current channel I02 resistive
current component.
I02 Reactive Current
p.u.
-1250.00…
1250.0xIn
0.01xIn Per unit measurement from residual current channel I02 reactive
current component.
Table. 5.2.1. - 24. Primary phase current component measurements
Name
Range
Step
Description
ILx Resistive Current
Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from each phase current channel resistive
current component.
ILx Reactive Current
Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from each phase current channel reactive
current component.
Pos.Seq Resistive
Current Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from each phase current channel resistive
current component.
Pos.Seq Reactive
Current Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from each phase current channel reactive
current component.
I01 Resistive Current
Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from residual current channel I01 resistive
current component.
I01 Reactive Current
Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from residual current channel I01 reactive
current component.
I02 Resistive Current
Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from residual current channel I02 resistive
current component.
I02 Reactive Current
Pri.
-100000.00 …
100000.00A
0.01A Primary measurement from residual current channel I02 reactive
current component.
Table. 5.2.1. - 25. Secondary phase current component measurements
Name
Range
Step
Description
ILx Resistive Current
Sec.
-300.00…
300.00A
0.01A Secondary measurement from each phase current channel resistive
current component.
ILx Reactive Current
Sec.
-300.00…
300.00A
0.01A Secondary measurement from each phase current channel reactive
current component.
Pos.Seq Resistive
Current Sec.
-300.00…
300.00A
0.01A Secondary measurement from each phase current channel resistive
current component.
AQ-F255
Instruction manual
Version: 2.00
25