Figure. 5.6.1. - 163. Simpli ed function block diagram of the CTS function.
Measured input values
Function block uses analog current measurement values. Function uses the fundamental frequency
magnitude of the current measurement inputs and calculated positive and negative sequence currents.
For residual current measurement can be selected: None, I01 fundamental component or I02
fundamental component.
Table. 5.6.1. - 217. Analogic magnitudes used by the CTS function.
Signal
Description
Time base
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
I01RMS
Fundamental RMS measurement of residual input I01
5 ms
I02RMS
Fundamental RMS measurement of residual input I02
5 ms
I1
Phase currents positive sequence component
5 ms
I2
Phase currents negative sequence component
5 ms
IL1Ang
Fundamental angle of phase L1/A current
5 ms
IL2 Ang
Fundamental angle of phase L2/B current
5 ms
IL3 Ang
Fundamental angle of phase L3/C current
5 ms
I01 Ang
Fundamental angle of residual input I01
5 ms
I02 Ang
Fundamental angle of residual input I02
5 ms
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
266