Alarm 2 Set
100 operations
With these settings Alarm 1 will be issued when any of the three phases cumulative interruptions
counter is below the set 1000 operations left and similarly when any of the counters is below the set
100 operations left Alarm 2 will be issued.
Events and registers
The CBW function generates events and registers from the status changes of Retrip, CBW activated
and blocked signals as well as from the internal pick-up comparators. To main event buffer is possible
to select status “On” or “Off” messages.
Function includes 12 last registers where the triggering event of the function is recorded with time
stamp and process data values.
Table. 5.6.5. - 233. Event codes of the CBW function instance
Event Number
Event channel
Event block name
Event Code
Description
3712
58
CBW1
0
CBWEAR1 Triggered
3713
58
CBW1
1
CBWEAR1 Alarm1 On
3714
58
CBW1
2
CBWEAR1 Alarm1 Off
3715
58
CBW1
3
CBWEAR1 Alarm2 On
3716
58
CBW1
4
CBWEAR1 Alarm2 Off
In the register of the CBW function recorded events are activated “On” event process data. In the table
below is presented the structure of CBW function register content. This information is available in 12
last recorded events for all provided instances separately.
Table. 5.6.5. - 234. Register content.
Date & Time
Event
code
Trigger current
All.Op.ITrg
Deduct. Op
Op.Left
dd.mm.yyyy
hh:mm:ss.mss
3713-3717
Descr.
Phase currents on
trigger time
Allowed operations with
trigger current
Deducted operations from
the cumulative sum
Operations
left
5.6.6. Fault locator (21FL) X
→
km
Fault locator is used for recording an estimated distance to the point where fault has occurred. It is
mostly used in directional overcurrent protection or distance protection applications but can be also
triggered by other protections as well. Function can be used if three phase current and three phase
voltage have been connected to the relay. In the con guration the triggering signals, triggering current
and reactance per km must be set.
Inputs for the function are the operating mode selections, setting parameters and measured and pre-
processed voltage and current magnitudes and binary input signals. The function registers its
operation into 12 last time-stamped registers and also generates general time stamped ON/OFF
events to the common event buffer from each of the three output signal. Time stamp resolution is 1ms.
Function provides also cumulative counter for fault locator triggering events.
Measured input values
Function block uses analog current and voltage measurements and calculated phase-to-phase loop
impedances.
AQ-F255
Instruction manual
Version: 2.00
291
© Arcteq Relays Ltd