3520
55
THD1
0
THD Start Phase On
3521
55
THD1
1
THD Start Phase Off
3522
55
THD1
2
THD Start I01 On
3523
55
THD1
3
THD Start I01 Off
3524
55
THD1
4
THD Start I02 On
3525
55
THD1
5
THD Start I02 Off
3526
55
THD1
6
THD Alarm Phase On
3527
55
THD1
7
THD Alarm Phase Off
3528
55
THD1
8
THD Alarm I01 On
3529
55
THD1
9
THD Alarm I01 Off
3530
55
THD1
10
THD Alarm I02 On
3531
55
THD1
11
THD Alarm I02 Off
3532
55
THD1
12
Blocked On
3533
55
THD1
13
Blocked Off
In the register of the THD function is recorded activated, blocked etc. “On” event process data. In the
table below is presented the structure of THD function register content. This information is available in
12 last recorded events for all provided instances separately.
Table. 5.6.7. - 245. Register content.
Date & Time
Event
code
IL1
THD
IL2
THD
IL3
THD
I01
THD
I02
THD
Ph
Trem
I01
Trem
I02
Trem
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
3521-3534
Descr.
Measured THD values on the trigger event.
Time left to Alarm on the
trigger event
1 - 8
5.6.8. Measurement value recorder
Measurement value recorder function records the value of selected magnitudes at the time of given
trigger signal. An example application for this function is to record fault currents or voltages at the time
of tripping the breaker but it can be used also to record the values from any user set trigger signal.
Value recorder is capable of recording either per unit value or primary value which is user settable.
Optionally it is possible to set the function to record the overcurrent or voltage fault type. The function
operates instantly from trigger signal.
Additionally, the measurement value recorder function has integrated fault display which displays the
current fault values in case of I>, Idir>, I0>, I0dir>, f<, f>, U< or U> trips. When any of these functions
trip fault values and fault type are displayed over the mimic view. The view can be enabled by activating
VREC Trigger On
in menu
Tools
→
Events and logs
→
Set alarm events
. Resetting of the fault values is
done by input selected in General menu.
Measured input values
Function block uses analog current and voltage measurement values. From these values relay
calculates the secondary and primary values of currents, voltages, powers, impedances and other
values.
Up to 8 magnitudes can be set to be recorded when function is triggered. Overcurrent fault type,
voltage fault type and tripped stage can be recorded and reported forward to SCADA.
AQ-F255
Instruction manual
Version: 2.00
297
© Arcteq Relays Ltd