By marking a dataset and pressing the Edit button the dataset edit dialog is opened. See following
picture. In the edit dialog all currently con gured entries of the dataset are visible. If the red ‘-‘-button is
pressed in the end of an entry row the entry will be removed from the dataset. If the green ‘±’-button is
pressed a new dialog is opened were it is possible to edit contents of the dataset. New entries can be
added and old edited. It is recommended that for URCB and BRCB datasets that data is selected on
the doName, data object level, (see example below). In this way all available information like; status,
quality and time is always sent in the report. Data can also be selected on daName, data attribute
level, selecting each individual data. This approach may be preferred for the GOOSE datasets.
Figure. 6.1.4. - 185. Data can be also chosen in data attribute level.
For more information on IEC 61850 support, see the conformance statement documents.
IEC61850 general parameters visible in AQtivate and local HMI are described in the table below.
Parameter
Range
Description
IEC61850 enable
[Disabled, Enabled]
Enable setting for IEC 61850 protocol.
IP port
[0…65535]
IP port used by IEC 61850 protocol. Standard and default port is 102.
Measurements dead-band
[0.01…10.00]
Measurement data reporting dead-band setting.
GOOSE subscriber enable
[Disabled, Enabled]
Enable setting for GOOSE subscriber.
6.1.5. GOOSE
Both GOOSE publisher and subscriber are supported by the Arcteq implementation. GOOSE
subscriber is enabled by parameter setting (
Communication
→
Protocols
→
IEC61850
→
GOOSE
subscriber enable
) and GOOSE inputs are con gured using HMI or Aqtivate tool. For each of the
Goose inputs there is also an input quality signal which can also be used in the internal logic. If the
input quality is low, (=0), then the quality is good. Input quality can be bad for reasons like GOOSE
timeout and con guration error. Logical input signal states and quality can be viewed in the device
under Device IO menu. For each GOOSE input following parameters are available.
Parameter
Range
Description
In use
[No, Yes]
Setting to take input in to use.
AppId
[0…
4294967295]
Application ID which will be matched with the publishers GOOSE control block.
AQ-F255
Instruction manual
Version: 2.00
305
© Arcteq Relays Ltd