System volt U3
mag
0.00…
1000000.00V
0.01V Primary measured fundamental frequency RMS Synchro-check SS voltage.
(Valid only in 2LL+U3+U4 mode)
System volt U4
mag
0.00…
1000000.00V
0.01V Primary measured fundamental frequency RMS Synchro-check SS voltage.
Table. 5.2.2. - 36. Voltage measurement angles.
Name
Range
Step
Description
System volt UL12
ang
0.00…
360.0deg
0.01deg Primary measured or calculated line to line UL12 angle.
System volt UL23
ang
0.00…
360.0deg
0.01deg Primary measured or calculated line to line UL23 angle.
System volt UL31
ang
0.00…
360.0deg
0.01deg Primary measured or calculated line to line UL31 angle.
System volt UL1 ang 0.00…
360.0deg
0.01deg Primary measured or calculated line to neutral UL1 angle.
System volt UL2 ang 0.00…
360.0deg
0.01deg Primary measured or calculated line to neutral UL2 angle.
System volt UL3 ang 0.00…
360.0deg
0.01deg Primary measured or calculated line to neutral UL3 angle.
System volt U0 ang
0.00…
360.0deg
0.01deg Primary measured or calculated zero sequence U0 angle.
System volt U3 ang
0.00…
360.0deg
0.01deg Primary measured Synchro-check SS angle. (Valid only in 2LL+U3+U4
mode)
System volt U4 ang
0.00…
360.0deg
0.01deg Primary measured Synchro-check SS angle.
Table. 5.2.2. - 37. Harmonic voltage measurements.
Name
Range
Step
Description
U1 Harmonics
U1 fund…U1
31harm
0.00…
100000.0V
0.01V Selectable per unit, primary and secondary harmonics per component for
voltage input U1
U2 Harmonics
U2 fund…U2
31harm
0.00…
100000.0V
0.01V Selectable per unit, primary and secondary harmonics per component for
voltage input U2
U3 Harmonics
U3 fund…U3
31harm
0.00…
100000.0V
0.01V Selectable per unit, primary and secondary harmonics per component for
voltage input U3
U4 Harmonics
U4 fund…U4
31harm
0.00…
100000.0V
0.01V Selectable per unit, primary and secondary harmonics per component for
voltage input U4
5.2.3. Power and energy calculation
IEDs with both voltage –and current cards can calculate power and have power based protection and
monitoring functions depending on the IED type. When power calculation is possible also the energy
magnitudes are calculated.
Power is divided into three magnitudes, apparent power S, active power P and reactive power Q.
Energy measurement is calculating magnitude for active and reactive energy. Energy can be flowing to
forward (exported) or reverse (imported) direction.
If unit has more than one CT measurement module it is possible to choose which side modules current
measurement is used by power calculation.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
34