L2 Exp.Active Energy Mwh
-1x10
9
…1x10
9
kWh/MWh
0.01
kWh/MWh
Phase L2 exported active energy
L2 Imp.Active Energy Mwh
-1x10
9
…1x10
9
kWh/MWh
0.01
kWh/MWh
Phase L2 imported active energy
L2 Exp/Imp.Act.E balance
Mwh
-1x10
9
…1x10
9
kWh/MWh
0.01
kWh/MWh
Sum of imported and exported phase L2 active
energy
L2 Exp.React.Cap.E.Mvarh
-1x10
9
…1x10
9
kVarh/MVarh
0.01
kVarh/MVarh
Phase L2total exported reactive capacitive energy
L2 Imp.React.Cap.E.Mvarh
-1x10
9
…1x10
9
kVarh/MVarh
0.01
kVarh/MVarh
Phase L2 total imported reactive capacitive energy
L2 Exp/Imp
React.Cap.E.bal.MVarh
-1x10
9
…1x10
9
kVarh/MVarh
0.01
kVarh/MVarh
Sum of imported and exported phase L2 reactive
capacitive energy
L2 Exp.React.Ind.E.Mvarh
-1x10
9
…1x10
9
kVarh/MVarh
0.01
kVarh/MVarh
Phase L2 total exported reactive inductive energy
L2 Imp.React.Ind.E.Mvarh
-1x10
9
…1x10
9
kVarh/MVarh
0.01
kVarh/MVarh
Phase L2 total imported reactive inductive energy
L2 Exp/Imp
React.Ind.E.bal.MVarh
kVarh/MVarh
0.01
kVarh/MVarh
Sum of imported and exported phase L2 reactive
inductive energy
Table. 5.2.3. - 48. Phase L3 energy calculation
Name
Range
Step
Description
L3 Exp.Active Energy Mwh
-1x10
6
…1x10
6
MWh
0.01
kWh/MWh
Phase L3 exported active energy
L3 Imp.Active Energy Mwh
-1x10
6
…1x10
6
MWh
0.01
kWh/MWh
Phase L3 imported active energy
L3 Exp/Imp.Act.E balance
Mwh
-1x10
6
…1x10
6
MWh
0.01
kWh/MWh
Sum of imported and exported phase L3 active energy
L3 Exp.React.Cap.E.Mvarh
-1x10
6
…1x10
6
MVarh
0.01
kVarh/MVarh
Phase L3total exported reactive capacitive energy
L3 Imp.React.Cap.E.Mvarh
-1x10
6
…1x10
6
MVarh
0.01
kVarh/MVarh
Phase L3 total imported reactive capacitive energy
L3 Exp/Imp
React.Cap.E.bal.MVarh
-1x10
6
…1x10
6
MVarh
0.01
kVarh/MVarh
Sum of imported and exported phase L3 reactive
capacitive energy
L3 Exp.React.Ind.E.Mvarh
-1x10
6
…1x10
6
MVarh
0.01
kVarh/MVarh
Phase L3 total exported reactive inductive energy
L3 Imp.React.Ind.E.Mvarh
-1x10
6
…1x10
6
MVarh
0.01
kVarh/MVarh
Phase L3 total imported reactive inductive energy
L3 Exp/Imp
React.Ind.E.bal.MVarh
-1x10
6
…1x10
6
MVarh
0.01
kVarh/MVarh
Sum of imported and exported phase L3 reactive
inductive energy
Calculation examples
Example for power calculation is represented here. Both wiring methods line to line –and line to neutral
are checked with same signal injection. Voltage scaling is set to 20000:100V and current scaling is set
to 1000:5A.
Voltages (Line to neutral):
Currents:
V
A
=40.825V, 45.00°
I
L1
=2.500V, 0.00°
V
B
=61.481V, -159.90°
I
L2
=2.500V, -120.00°
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
40