Freq.Reference
3
0:None
1:CT1IL3
2:CT2IL3
3:VT1U3
4:VT2U3
-
CT1IL3
Frequency tracking reference source 3
Freq tracker
quality
0:No
trackable
channels
1:Reference
1 Trackable
2:Reference
2 Trackable
3:Reference
1&2
Trackable
4:Reference
3 Trackable
5:Reference
1&3
Trackable
6:Reference
2&3
Trackable
7:All
References
Trackable
-
-
Frequency tracker quality. If the current or voltage measured
amplitude is below the threshold channel tracking quality is 0 and
cannot be used for frequency tracking. If all channels magnitudes are
below threshold there will be no trackable channels.
Start behavior
0:Start
tracking
immediately
1:Use nom
or tracked
-
0:Start
tracking
immediately
Start behavior of the frequency tracked. Can be set so that the
tracking is started after set delay from the receiving of rst trackable
channel or tracking start immediately.
Start sampling
with
0:Use track
freq
1:Use nom
freq
-
0:Use track
freq.
Start of sampling selection, can be either previously tracked
frequency or user set nominal frequency.
Use nom. freq.
until
0…
1800.000s
0.005s 0.100s
Setting how long nominal frequency is used when starting tracking.
Setting is valid if tracking mode is active and start behavior is “Use
nom or tracked”
Tracked F CHA 5…75.0Hz
0.1Hz
-
Display of the channel A tracked frequency, rough value.
Tracked F CHB 5…75.0Hz
0.1Hz
-
Display of the channel B tracked frequency, rough value.
Tracked F CHC 5…75.0Hz
0.1Hz
-
Display of the channel C tracked frequency, rough value.
5.3. General menu
General-menu consists of basic settings and indications of the IED. In addition to this protection,
control and monitor pro le displays activated functions and their status.
Table. 5.3. - 51. Parameters and indications in General-menu
Name
Description
Range
Step
Default
Device name
When loading the aqs con guration le from the AQ-200 unit the le
name uses these elds.
-
-
Unitname
Device
location
-
-
Unitlocation
Timesync.
source
If external clock time synchronization source is available, the type is
de ned with this parameter. In internal mode there is no external
Timesync source. IRIG-B requires serial ber communication option
card.
0:Internal
1:External
NTP
2:External
Serial
3:IRIG-B
-
0:Internal
Enable stage
forcing
When this parameter is enabled it is possible for the user to force
protection, control and monitoring functions to different statuses like
START/TRIP. This is done in the function’s info-page with Status force
to parameter.
0:Disabled
1:Enabled
-
0:Disabled
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
44