Operating time characteristics for trip and reset
This function supports instant operation, de nite time delay (DT) and inverse de nite minimum time
(IDMT) delay types. For detailed information on these delay types refer to chapter General properties of
a protection function.
Events and registers
The DOC function generates events and registers from the status changes of start, trip and blocked.
To main event buffer is possible to select status “On” or “Off” messages. The DOC function offers four
independent instances which events are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function (start, trip or
blocked) is recorded with time stamp and process data values.
Table. 5.4.4. - 73. Event codes of the DOC function instances 1 – 4.
Event Number
Event channel
Event block name
Event Code
Description
4800
75
DOC1
0
Start ON
4801
75
DOC1
1
Start OFF
4802
75
DOC1
2
Trip ON
4803
75
DOC1
3
Trip OFF
4804
75
DOC1
4
Block ON
4805
75
DOC1
5
Block OFF
4806
75
DOC1
6
No voltage, Blocking On
4807
75
DOC1
7
Voltage measurable, Blocking Off
4808
75
DOC1
8
Measuring live angle On
4809
75
DOC1
9
Measuring live angle Off
4810
75
DOC1
10
Using voltmem On
4811
75
DOC1
11
Using voltmem Off
4864
76
DOC2
0
Start ON
4865
76
DOC2
1
Start OFF
4866
76
DOC2
2
Trip ON
4867
76
DOC2
3
Trip OFF
4868
76
DOC2
4
Block ON
4869
76
DOC2
5
Block OFF
4870
76
DOC2
6
No voltage, Blocking On
4871
76
DOC2
7
Voltage measurable, Blocking Off
4872
76
DOC2
8
Measuring live angle On
4873
76
DOC2
9
Measuring live angle Off
4874
76
DOC2
10
Using voltmem On
4875
76
DOC2
11
Using voltmem Off
4928
77
DOC3
0
Start ON
4929
77
DOC3
1
Start OFF
4930
77
DOC3
2
Trip ON
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
72