In the register of the HOC function is recorded start, trip or blocked “On” event process data. In the
table below is presented the structure of HOC function register content. This information is available in
12 last recorded events for all provided instances separately.
Table. 5.4.8. - 98. Register content
Date & Time
Event
code
Fault type
Trigger
current
Fault
current
Prefault
current
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
2368-2565
Descr.
L1-G …
L1-L2-L3
Start average
current
Trip -20 ms
averages
Start -200 ms
averages
0ms -1800s
1 - 8
5.4.9. Circuit breaker failure protection CBFP (50BF)
Circuit breaker failure protection (CBFP) function is used for monitoring the circuit breaker operation
after it has been tripped. CBFP function can be used for Retrip to the failing breaker and if the Retrip
fails the upstream breaker can be tripped by using CBFP output. Retrip functionality can be disabled if
the breaker does not have two open coils.
CBFP function can be triggered from overcurrent (phases and residual), digital output monitor, digital
signal or combination of these mentioned triggers.
In current dependent mode CBFP function constantly measures phase current magnitudes and
selected residual current. In signal dependent mode any of the IED binary signal can be used for
triggering the CBFP. In binary output dependent mode CBFP monitors selected output relay control
signal status. Blocking signal and setting group selection controls the operating characteristics of the
function during normal operation.
Outputs of the function are CBFP START, RETRIP, CBFP ACT and BLOCKED signals. Setting
parameters are static inputs for the function which are changed only by user input in the setup phase
of the function. CBFP function utilizes total of eight separate setting groups which can be selected from
one common source. Also the operating mode of the CBFP can be changed by setting group
selection.
The operational logic consists of input magnitude processing, threshold comparator, block signal
check, time delay characteristics and output processing.
Inputs for the function are setting parameters and measured and pre-processed current magnitudes
and binary input and output signals. Function output signals can be used for direct IO controlling and
also for user logic programming. The function registers its operation into 12 last time-stamped registers
and also generates general time stamped ON/OFF events to the common event buffer from each of the
two output signal. Time stamp resolution is 1ms. Function provides also cumulative counters for
RETRIP, CBFP, CBFP START and BLOCKED events.
AQ-F255
Instruction manual
Version: 2.00
101