4.2. User level password con guration
As a factory default IEDs do not have any user levels locked behind passwords. In order to activate
different user levels click the IED HMI lock button and set the desired passwords for different user
levels.
NOTE: Passwords can be set only at local HMI.
In the HMI the user level currently in use is indicated in the upper right corner with stars.
Different user levels and the indicators are:
SUPERUSER (***) = full access including con gurations
CONFIGURATOR (**) = access to all settings
OPERATOR (*) = access to limited settings and control
USER ( - ) = view only
You can set a new password for the user level by selecting the key icon next to the user level. After this
you can lock the user level by pressing return key while the lock is selected. If you need to change the
password you can select the key icon again and give a new password. Please note that in order to do
this the user level must be unlocked.
The required access level required to change a parameter is indicated with star (*) symbol if such is
required. As a general rule the access levels are divided as follows:
User:
Can view any menus and settings but cannot change any settings nor operate breakers
or other equipment.
Operator:
Can view any menus and settings but cannot change any settings BUT can operate
breakers or other equipment.
Con gurator:
Can change most settings like basic protection pick-up levels or time delays,
breaker control functions, signal descriptions etc. Can operate breakers or other equipment.
Super user:
Access to change any setting and can operate breakers or other equipment.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
10