Table. 5.4.10. - 108. Event codes of the REF function instance
Event Number
Event channel
Event block name
Event Code
Description
4224
66
REF1
0
REF Trip On
4225
66
REF1
1
REF Trip Off
4226
66
REF1
2
REF Block On
4227
66
REF1
3
REF Block Off
In the register of the REF function is recorded activated, blocked etc. “On” event process data. The
structure of REF function register content is presented in the table below. This information is available
in 12 last recorded events for all provided instances separately.
Table. 5.4.10. - 109. Register content
Date & Time
Event code
Trigger currents
Trigger currents
Residual
currents
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
4224-4227
Descr.
Biascurrent trig
Diffcurrent trig
Characteristics diff
trig
Biascurrent max
Diffcurrent max
Characteristics diff
max
I0Calc
I0 meas
1 - 8
5.4.11. Overvoltage U> (59)
Overvoltage function (OV) is used for instant- and time delayed overvoltage protection for various
applications including feeder, lter and machine applications of utilities and industry. Each IED with
voltage protection module has four available instances of the function (U>, U>>, U>>>, U>>>>).
Function measures constantly phase voltage magnitudes or line- to line voltage magnitudes.
Overvoltage protection is based to line- to line fundamental frequency component or to line- to neutral
fundamental frequency component if so chosen. If protection is based to line- to line voltage, during
earth fault in isolated or compensated networks the overvoltage protection is not affected. Blocking
signal and setting group selection controls the operating characteristics of the function during normal
operation.
Outputs of the function are Start Trip and Blocked signals. Setting parameters are static inputs for the
function which are changed only by user input in the setup phase of the function. Overvoltage function
utilizes total of eight separate setting groups which can be selected from one common source.
The function can be operating on instant or time delayed mode. In time delayed mode the operation
can be selected for de nite time or IDMT.
The operational logic consists of input magnitude processing, input magnitude selection, threshold
comparator, block signal check, time delay characteristics and output processing.
Inputs for the function are the operating mode selections, setting parameters and measured and pre-
processed voltage magnitudes and binary input signals. Function outputs START, TRIP and BLOCKED
signals which can be used for direct IO controlling and also for user logic programming. The function
registers its operation into 12 last time-stamped registers and also generates general time stamped
ON/OFF events to the common event buffer from each of the three output signal. In instant operating
mode the function outputs START and TRIP events simultaneously with equivalent time stamp. Time
stamp resolution is 1ms. Function provides also cumulative counters for START, TRIP and BLOCKED
events.
In the following gure is presented the simpli ed function block diagram of the OV function.
AQ-F255
Instruction manual
Version: 2.00
121