Alarm1 inits
Times the TOLF function has activated the Alarm 1 output
Alarm2 inits
Times the TOLF function has activated the Alarm 2 output
Restart inhibits
Times the TOLF function has activated the Restart inhibit output
Trips
Times the TOLF function has tripped
Trips Blocked
Times the TOLF function trips has been blocked
Events and registers
The TOLF function generates events and registers from the status changes of the Trip activated and
blocked signals. To main event buffer is possible to select status “On” or “Off” messages.
In the function is available 12 last registers where the triggering event of the function (Trip activated or
blocked) is recorded with time stamp and process data values.
Table. 5.4.21. - 170. Event codes of the TOLF function instance
Event Number
Event channel
Event block name
Event Code
Description
4288
67
TOLF1
0
Alarm1 On
4289
67
TOLF1
1
Alarm1 Off
4290
67
TOLF1
2
Alarm2 On
4291
67
TOLF1
3
Alarm2 Off
4292
67
TOLF1
4
Inhibit On
4293
67
TOLF1
5
Inhibit Off
4294
67
TOLF1
6
Trip On
4295
67
TOLF1
7
Trip Off
4296
67
TOLF1
8
Block On
4297
67
TOLF1
9
Block Off
In the register of the TOLF function is recorded activated, blocked etc. “On” event process data. In the
table below is presented the structure of TOLF function register content. This information is available in
12 last recorded events for all provided instances separately.
Table. 5.4.21. - 171. Register content
Date & Time
Event
code
Time to reach 100%
theta
Ref. T current
Active meas
current
T at the
moment
dd.mm.yyyy
hh:mm:ss.mss
4288- 4297 Descr.
seconds
xIn
xIn
%
Max temp rise allowed
Temp rise at the
moment
Hot Spot estimate
Hot spot max
all.
Trip delay rem
Used SG
deg
deg
deg
deg
s
1 - 8
5.4.22. Voltage memory function
Certain protection functions such as, impedance or directional overcurrent, are using the current and
voltage measured at the relay to determine if the electrical network fault appears to be inside protected
area. The determination is made by comparing the angle between the operating quantity (zone/trip
area) to actual measured quantity. The function will produce an output in case required terms are met.