9.2. Functions
9.2.1. Protection functions
9.2.1.1. Non-directional overcurrent (50/51) I>
Table. 9.2.1.1. - 279. Non-directional overcurrent (50/51) technical data
Input signals
Input magnitudes
Phase current fundamental freq RMS
Phase current TRMS
Phase current peak-to-peak
Pick-up
Pick-up current setting
0.10…50.00 x In, setting step 0.0001 x In
0.10…50.00%I
1f
, setting step 0.01 %I
1f
Inaccuracy
-Current
-2
nd
harmonic
±0.5 %I
SET
or ±15 mA (0.10…4.0 x I
SET
)
±1.0 %-unit of 2nd harmonic setting
Operation time
De nite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy
-De nite Time (Im/Iset ratio > 3)
-De nite Time (Im/Iset ratio 1.05…3)
±1.0 % or ±20 ms
±1.0 % or ±30 ms
IDMT operating time setting (ANSI / IEC)
0.02…1800.00 s, setting step 0.001 x parameter
IDMT setting parameters
k Time dial setting for IDMT
A IDMT Constant
B IDMT Constant
C IDMT Constant
0.01…25.00 step 0.01
0…250.0000 step 0.0001
0…5.0000 step 0.0001
0…250.0000 step 0.0001
Inaccuracy
-IDMT operating time
-IDMT minimum operating time; 20 ms
±1.5 % or ±20 ms
±20 ms
Retardation time (overshoot)
<25 ms
Instant operation time
Start time and instant operation time (trip):
(Im/Iset ratio > 3)
(Im/Iset ratio 1.05…3)
<35 ms (typically 25 ms)
<50 ms
Reset
Reset ratio
97 % of pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010 … 10.000 s, step 0.005 s
±1.0 % or ±50 ms
Instant reset time and start-up reset
<50 ms
Note!
Release delay does not apply on phase speci c tripping.
9.2.1.2. Non-directional earth fault (50N/51N) I0>
Table. 9.2.1.2. - 280. Non-directional earth-fault (50N/51N) technical data
Input signals