When
grounded
mode is active
-Trip area center
-Trip area size (+/-)
0.00…360.00 deg, setting step 0.10 deg
45.00…135.00 deg, setting step 0.10 deg
Pick-up current setting
Pick-up voltage setting
0.005…40.00 x In, setting step 0.001 x In
1.00…50.00 % U0n, setting step 0.01 x In
Inaccuracy
Starting I01 (1 A)
Starting I02 (0.2 A)
Starting I0Calc (5 A)
Voltage U0 and U0Calc
U0/I0 angle (U > 15 V)
U0/I0 angle (U = 1…15 V)
±0.5 %I0
SET
or ±3 mA (0.005…10.0 x I
SET
)
±1.5 %I0
SET
or ±1.0 mA (0.005…25.0 x I
SET
)
±1.5 %I0
SET
or ±15 mA (0.005…4.0 x I
SET
)
±2.5 %U0
SET
±0.1 ° (I0Calc ±1.0 °)
±1.0 °
Operation time
De nite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy
De nite Time (Im/Iset ratio 1.05
→
)
±1.0 % or ±45 ms
IDMT operating time setting (ANSI / IEC)
0.02…1800.00 s, setting step 0.001 x parameter
IDMT setting parameters
k Time dial setting for IDMT
A IDMT Constant
B IDMT Constant
C IDMT Constant
0.01…25.00 step 0.01
0…250.0000 step 0.0001
0…5.0000 step 0.0001
0…250.0000 step 0.0001
Inaccuracy
IDMT operating time
IDMT minimum operating time; 20 ms
±1.5 % or ±20 ms
±20 ms
Instant operation time
Start time and instant operation time (trip):
(Im/Iset ratio > 3)
(Im/Iset ratio 1.05…3)
<50 ms (typical 40 ms)
<65 ms
Reset
Current and voltage reset
U0/I0 angle
97 % of pick-up current and voltage setting
2.0 °
Reset time setting
Inaccuracy: Reset time
0.000 … 150.000 s, step 0.005 s
±1.0 % or ±45 ms
Instant reset time and start-up reset
<50 ms
9.2.1.5. Intermittent earth fault (67NT) IoInt>
Table. 9.2.1.5. - 283. Intermittent earth-fault (67NT) technical data
Input signals
Input current magnitudes
Input voltage magnitude
Residual current samples
Zero sequence voltage samples
Pick-up settings
Used current magnitude
Used voltage magnitude
Measured residual current I01 (1 A)
Measured residual current I02 (0.2 A)
Measured zero sequence voltage U0
Spikes to trip
1…50, setting step 1
Pick-up current setting
Pick-up voltage setting
0.05…40.00 x In, setting step 0.001 x In
1.00…100.00 % U0n, setting step 0.01 x In
Pick-up inaccuracy
AQ-F255
Instruction manual
Version: 2.00
347
© Arcteq Relays Ltd