9.2.1.17. Over/Under/Reverse power protection (32/37) P>, P<, PREV>
Table. 9.2.1.17. - 295. Power (32/37) technical data
Input signals
Input magnitudes
Phase current and voltage fundamental freq RMS
Pick-up
P>
P
REV
>
0.10…150000.00 kW, setting step 0.01 kW
-15000.00…-1.00 kW, setting step 0.01 kW
P<
Low Power block Pset<
0.00…150000.00 kW, setting step 0.01 kW
0.00…100000.00 kW, setting step 0.01 kW
Inaccuracy
-Active power
Typically <1.0 %P
SET
Operation time
De nite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy
-De nite Time (Pm/Pset ratio 1.05
→
)
±1.0 % or ±35 ms
Instant operation time
Start time and instant operation time (trip):
(Pm/Pset ratio 1.05
→
)
<50 ms
Reset
Reset ratio
0.97/1.03 x Pset
Reset time setting
Inaccuracy: Reset time
0.000 … 150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
Note!
Voltage measurement starts from 0.5V and current measurement from 50mA. In case either or
both is missing the power measurement is forced to 0kW. In case the settings allow (low power
block = 0 kW), the P< might be on trip state during this condition. Trip is released when voltage
and current is started to measure.
When low power block is set to zero it is not in use. Also power measurement below 1.00 kW is
forced to zero (P< blocked).
9.2.1.18. Resistance temperature detector alarm (49RTD) T>
Table. 9.2.1.18. - 296. Resistance temperature detector alarm (49RTD) technical data
Inputs
Input magnitudes
Measured temperatures
Alarm channels
12 individual alarm channels
Settable alarms
Two per each channel total of 24 alarms available
Pick-up
Alarm setting range
Inaccuracy
Reset ratio
101.00…2000.00 deg, setting step 0.1 deg either under or over setting.
±3% of set pick-up value
97% of the pick-up setting
Operation
Operating time
Typically <500 ms
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
356