Reset
Reset ratio for current
97 %
Reset time
<35 ms
Note!
Arc sensor maximum cable length is 200 meters.
9.2.2. Control functions
9.2.2.1. Setting group selection
Table. 9.2.2.1. - 299. Setting group selection technical data
Settings and control modes
Setting groups
8 independent control prioritized setting groups
Control scale
Common for all installed functions which support setting groups
Control mode
Local
Any digital signal available in the device
Remote
Force change overrule of local controls either from setting tool, HMI or SCADA
Operation time
Reaction time
<5 ms from receiving the control signal
9.2.2.2. Object control (OBJ)
Table. 9.2.2.2. - 300. Object control (OBJ) technical data
Signals
Input signals
Binary inputs
Software signals
Output signals
Close command output
Open command output
Operation time
Breaker traverse time setting
0.02…500.00 s, setting step 0.02 s
Max close/open command pulse length
0.02…500.00 s, setting step 0.02 s
Control termination time out setting
0.02…500.00 s, setting step 0.02 s
Inaccuracy
De nite Time operating time
±0.5 % or ±10 ms
Breaker control operation time
External object control time
<75ms
Object control during Autoreclosing
See Autoreclosing technical sheet
9.2.2.3. Autoreclosing function (79) 0
→
1
Table. 9.2.2.3. - 301. Autoreclosing function (79) technical data
Input signals
Input signals
Software signals (Protection, Logics, etc.)
Binary inputs
Requests
AQ-F255