Maximum active time
0.020…50.000 s, setting step 0.005 s
Inaccuracy
De nite Time (Um/Uset ratio >1.05)
±1.0 % or ±35 ms
Angle memory
Angle drift while voltage is absent
±1.0 ° per 1 second
Reset
Reset ratio
Voltage memory (voltage)
Voltage memory (current)
103 % of pick-up voltage setting
97 % of pick-up current setting
Reset time
<50 ms
9.3. Tests and environmental
Electrical environment compatibility
Table. 9.3. - 312. Disturbance tests
All tests
CE approved and tested according to EN 60255-26
Emissions
Conducted emissions
EN 60255-26 Ch. 5.2, CISPR 22
150kHz - 30 MHz
Radiated emissions
EN 60255-26 Ch. 5.1, CISPR 11
30 - 1 000 MHz
Immunity
Electrostatic discharge (ESD):
EN 60255-26, IEC 61000-4-2
Air discharge 15 kV
Contact discharge 8 kV
Fast transients (EFT):
EN 60255-26, IEC 61000-4-4
Power supply input 4kV, 5/50ns, 5kHz
Other inputs and outputs 4kV, 5/50ns, 5kHz
Surge:
EN 60255-26, IEC 61000-4-5
Between wires 2 kV / 1.2/50µs
Between wire and earth 4 kV / 1.2/50µs
Radiated RF electromagnetic eld:
EN 60255-26, IEC 61000-4-3
f = 80….1000 MHz 10V /m
Conducted RF eld:
EN 60255-26, IEC 61000-4-6
f = 150 kHz….80 MHz 10V
Table. 9.3. - 313. Voltage tests
Dielectric voltage test
EN 60255-27, IEC 60255-5, EN 60255-1
2 kV, 50Hz, 1min
Impulse voltage test
EN 60255-27, IEC 60255-5
5 kV, 1.2/50us, 0.5J
Physical environment compatibility
Table. 9.3. - 314. Mechanical tests
Vibration test
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
364