System
phase
rotating order
Allows the user to switch the expected order in which the phase
measurements are wired to the unit.
0:A-B-C
1:A-C-B
-
0:A-B-C
Language
Changes the parameter description languages in the HMI.
0:User
de ned
1:English
2:Suomi
3:Svenska
4:Español
5:Français
-
1:English
Clear events
Clears the event history recorded in the AQ-200 IED.
0:-
1:Clear
-
0:-
Display
brightness
Changes the display brightness.
0…8
1
4
Return to
default view
If user navigates to a menu and gives no input after a period of time
de ned with this parameter the unit will return to default view
automatically. If time is set to 0s this feature is not in use.
0…3600s
10s
0s
Reset latches Resets latched signals in the logic and matrix. When reset command is
given the parameter will return back to “-“ automatically.
0:-
1:Reset
-
0:-
Measurement
recorder
Enables Measurement recorder tool. Measurement recorder is
con gured in
Tools
→
Misc
→
Measurement recorder.
0:Disabled
1:Enabled
-
0:Disabled
MIMIC
recon gure
Reload the mimic to the unit.
0:-
1:Recon gure -
0:-
Table. 5.3. - 52. General-menu indications
Name
Description
Serial number
Unique serial number identi cation of the unit.
SW version
Units rmware software version.
HW conf.
Units order code identi cation.
UTC time
UTC time value which IED clock uses.
5.4. Protection functions
5.4.1. General properties of a protection function
Following flowchart is describes the basic structure of any protection function. Basic structure is
composed of analog measurement value comparison to the pick-up values and operating time
characteristics.
AQ-F255
Instruction manual
Version: 2.00
45
© Arcteq Relays Ltd