When only U3 or U4 voltage measurement channel has been set to "SS" mode:
• SYN1 – Supervises the synchronization condition between the channel set to "SS" mode and
the selected system voltage (UL1, UL2, UL3, UL12, UL23 or UL31).
• SYN2 – Not active and not visible.
• SYN3 – Not active and not visible.
When both U3 and U4 have been set to "SS" mode:
• SYN1 – Supervises the synchronization condition between the U3 channel and the selected
system voltage (UL1, UL2, UL3, UL12, UL23 or UL31).
• SYN2 – Supervises the synchronization condition between the U4 channel and the selected
system voltage (UL1, UL2, UL3, UL12, UL23 or UL31).
• SYN3 – Supervises the synchronization condition between the channels U3 and U4.
The seven images below present three different example connections and four example applications of
the synchrocheck function.
Figure. 5.4.4 - 193. Example connection of the synchrocheck function (3LN+U4 mode, SYN1 in use, UL1 as reference voltage).