Name
Range
Step
Description
Voltage meas
selected
0: Selection Ok
1: Selection not
available
-
Displays validity of the voltage channel(s) selected in "Monitored
voltages" parameter.
Δα > U1 Angle
difference
-360...360deg
0.01deg Displays the angle difference between present time and 20 ms ago.
Δα > U2 Angle
difference
Δα > U3 Angle
difference
Δα > U1meas/set
-360...360p.u.
0.01p.u. Displays the ratio between the measured voltage and undervoltage
block limit setting.
Δα > U2meas/set
Δα > U3meas/set
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when
the pick-up element activates, a ALARM or TRIP signal is generated and the function proceeds to the
time characteristics calculation.
If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further.
The blocking of the function causes an HMI display event and a time-stamped blocking event with
information of the startup voltage values and its fault type to be issued.
The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
Events and registers
The vector jump function (abbreviated "VJP" in event block names) generates events and registers from
the status changes in START, TRIP, and BLOCKED. The user can select which event messages are
stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.6 - 224. Event codes.
Event number
Event channel
Event block name
Event code
Description
9920
155
VJP1
0
Block ON
9921
155
VJP1
1
Block OFF
9922
155
VJP1
2
Trip ON
9923
155
VJP1
3
Trip OFF
9924
155
VJP1
4
Alarm ON
9925
155
VJP1
5
Alarm OFF
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
329