Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 1.05
→
)
±1.0 % or ±25 ms
IDMT setting parameters:
k Time dial setting for IDMT
A IDMT constant
B IDMT constant
C IDMT constant
0.01…25.00, step 0.01
0…250.0000, step 0.0001
0…5.0000, step 0.0001
0…250.0000, step 0.0001
Inaccuracy:
- IDMT operating time
- IDMT minimum operating time
±1.5 % or ±20 ms
±20 ms
Instant operation time
Start time and instant operation time (trip):
- I
M
/I
SET
ratio 1.05
→
<40 ms
Reset
Reset ratio:
- Current
97 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.000…150.000 s, step 0.005 s
±1.0 % or ±25 ms
Instant reset time and start-up reset
<45 ms
9.2.1.17 100 % stator earth fault protection (U03rd>; 64S)
Table. 9.2.1.17 - 325. Technical data for the 100 % stator earth fault protection function.
Measurement updates
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input calculation
Positive sequence current (I1)
Voltage inputs
Residual voltage from U3 or U4 voltage channel
Voltage input magnitude
Zero sequence voltage third harmonic
Pick-up
Pick-up voltage setting
1.00…95.00 %U0
N
, setting step 0.01 %U0
N
Inaccuracy:
- U0 3rd harmonic
±1.0 %U0
SET
or ±50 mV
Low-current blocking
"No load" current setting
0.00…1.00 × I
N
, setting step 0.01 × I
N
Inaccuracy:
- Starting (I1)
±1.0 %I1
SET
or ±100 mA (0.10…4.0 × I
N
)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 0.95)
±1.0 % or ±30 ms
Instant operation time
Start time and instant operation time (trip):
- U
M
/U
SET
ratio <0.95
<60 ms