Pick-up setting
-1 000 000.00…0.00 kVar, setting step 0.01 kVar
Inaccuracy:
- Reactive power
Typically <1.0 %Q
SET
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (Q
M
/Q
SET
ratio 1.05
→
)
±1.0 % or ±35 ms
Instant operation time
Start time and instant operation time (trip):
- Q
M
/Q
SET
ratio <0.95
<50 ms
Reset
Reset ratio
97 % of the set pick-up value
Reset time setting
Inaccuracy: Reset time
0.000…150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
No
Notte!
e!
• Voltage measurement starts from 0.5 V and current measurement from 50 mA. If either or
both are missing the reactive power measurement is 0 kVar.
9.2.1.22 Arc fault protection (IArc>/I0Arc>; 50Arc/50NArc) (optional)
Table. 9.2.1.22 - 330. Technical data for the arc fault protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Residual current channel I
01
(Coarse)
Residual current channel I
02
(Fine)
Current input magnitudes
Sample-based phase current measurement
Sample-based residual current measurement
Arc point sensor inputs
Channels S1, S2, S3, S4 (pressure and light sensor, or light-only sensor)
Up to four (4) sensors per channel
System frequency operating range
6.00…75.00 Hz
Pick-up
Pick-up current setting (phase current)
Pick-up current setting (residual current)
Pick-up light intensity
0.50…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
8, 25 or 50 kLx (the sensor is selected in the order code)
Starting inaccuracy (IArc> and I0Arc>)
±3 % of the set pick-up value > 0.5 × I
N
setting. 5 mA < 0.5 × I
N
setting.
Point sensor detection radius
180 degrees
Operation time
Light only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (3…12 ms)
Typically 10 ms (6.5…15 ms)
Light + current criteria (zone 1…4):
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 10 ms (6.5…14 ms)
Typically 14 ms (10…18 ms)
Arc BI only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (2…12 ms)
Typically 10 ms (6.5…15 ms)
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
446