Instruction manual
–
AQ G3x7 Generator protection IED
170 (211
)
DLD_
DeadLine_
GrI_
DLD_StIL3_GrI
_
DLD_StIL2_GrI
_
DLD_StIL1_GrI
_
DLD_StUL3_GrI
_
DLD_StUL2_GrI
_
DLD_StUL1_GrI
_
DLD_
LineOK_GrI_
VTS_
Fail_GrI_
VTS_Fail_int_
NOT
OR
AND
t
200
t
100
t
100
S
R
AND
NOT
NOT
OR
S
R
OR
AND
VTS_Blk_GrO_
Figure 3-101: Decision logic of the voltage transformer supervision function.
NOTE: For the operation of the voltage transformer supervision function the
“
Dead line
detection function
”
must be operable as well: it must be enabled by binary parameter
1.1.1.2
The symbol of the function block in the AQtivate 300 software
The function block of voltage transformer supervision function is shown in figure below. This
block shows all binary input and output status signals that are applicable in the graphic
equation editor.
Figure 3-102: The function block of the voltage transformer supervision function
The binary input and output status signals of voltage transformer supervision function are
listed in tables below.